In accordance with the Government of India, Ministry of Environment and Forests' notification on Batteries (Management & Handling) Rules, 2001, it is the responsibility of every consumer to ensure that used Lead- Acid Batteries are not disposed -off in any manner other than returning to Dealer for recycling of hazardous lead content. Please contact your Dealer for trade-in purpose.
Shall be the responsibility of the consumer to ensure that used batteries are not disposed of in any manner other than depositing with the dealer, manufacturer, importer, assembler, registered recycler, re-conditioner or at the designated collection centres.
Battery Type | Warranty In Months |
---|---|
LMXT300 | 36 |
LMXT400 | |
LMXT500 | |
LMXT550 | |
LMXT600 | |
LMXT650 | |
LMXT700 | |
LMXT750 | |
LMXT800 | |
LMXT850 | |
LMXT900 | |
LMXT1000 |
Charging Current | Maximum - 20% of the battery Ah capacity Minimum - 10% of the battery AH capacity |
Bulk Voltage | 2.60 +/- 0.02V x no. of cells |
Float Voltage | 2.30 +/- 0.02V x no. of cells |
Load Reconnect Voltage | 2.16 +/- 0.02V x no. of cells |
Low Voltage Disconnect | 1.90 +/- 0.02V x no. of cells |
Recharge Factor | 110% of discharge Ah |
Temperature Correction Factor (reference 25ºC) |
Float: -3mV/°C/2V unit Cyclic: -5mV/°C/2V unit |